Infra-Red Temperature Control Systems for A/C, Heat Pump & 2/4 pipe Fan Coils A9
Extremely flexible, based on a common Power Board with various Interface Control Options – plug & play:
Standard Power Board Control & Specification - (Customisation is an option)
Temp. Settings: Ranges: 10 – 30 °C: Deadband: +/- 0.5 °C: Diffs: +/- 0.5 °C
Inputs: Power: 230 Vac Sensors: R/A – O/C – D/A Fault: optional
Relay Outputs: Cooling – Heating (or Reversing Valve) - 2nd stage Heating (option)* - 2.5 hp cooling (option)*
{6(3) A @ 230 Vac}. * If 2.5 hp. relay specified 2
nd
. Stg htg. not available.
3 x Indoor Fan Speeds - Outdoor Fan - Swing (option)
Time Delays: 3 mins. (+/_) on cooling function. (+/-) times vary slightly for recycling purposes.
Defrost progs. Indoor coil; –1 to +8 °C Outdoor Coil: 0 to 16 °C - 5/22 mins. max duration/sample
Timer Programmes: Daily 1 x Start Stop per day with manual override facility (standard transmitter).
Weekly: 2 x Start / Stops per day for periods: Mon. to Fri. + Sat. + Sun.
MIGA...
Infra-Red Receiver
Transmitter
Surface Mount
Flush Mount
Inter-Face Control Options
Transmitter; For remote control of all the functions detailed above.
IRT03. - daily programme
Receiver: Receives instructions from transmitter & relays them to Power Board
There are two types:
IRP– small plastic module (ideal ceiling /grill mtg.)
MIP – Adhesive Vinyl (ideal for surface mtg.)
User Interface Control: (Option of additional Infra-red control function available)
Available as Surface or Flush mounting unit allows them to be mounted either as integral part of
the A/C unit etc. or remotely
MIGAETN - Surface mount
MIGAFMH - Flush mount
Systems incorporating Humidity Control in addition to Temperature Control
These systems are available – please contact office for fuller details.
Options: Remote Temp. sensors – See page 18
SCI (UK) Ltd. Manx House, Bousley Rise, Ottershaw, Surrey, KT16 0JX, England.
Tel / Fax: +44 (0) 1932 875227 & 5, E mail; [email protected].uk, Web-site: www.sciuk.co.uk